kimley-horn.com 11400 Commerce Park Drive, Suite 400, Reston, VA 20191 703 674 1300
February 27, 2026
To: County of Frederick, Virginia
Re: Comment Response Site Plan #48-25: Firestone Auto Center
Dear Eric Bittner
Please find the following responses addressing comments received in letters from various county and
state departments:
Department of Planning and Development
Comment 1a: Provide the Power of Attorney with wet signatures. Not addressed, received
was a photo-copy, a wet signature copy is still required.
Response 1a:
Power of Attorney with wet signatures has been included with
this submission package.
Comment 4a: Parking space location. Provide the parking setback lines on the site plan.
(§165-202-01(D)(6)). Parking setbacks apply to all four sides of the
property. Partially addressed, parking setbacks apply to other property lines.
Response 4a: Per correspondence with Eric on February 19th, “Interior lot
lines aren't exempt from the parking standards: they have a
5' setback (from the property line) rather 10' from the ROW
line.” 5’ setbacks have been added to the plans. The access
drive to the east is now a named roadway. As such,
setbacks are now shown along that boundary.
Comment 4c: Setback: Include the actual setbacks for all property lines. Partially addressed.
Provide the actual distance from the building to each property line.
Response 4c: Actual distances from the building to each property line/
egress easement have been added to the plans. See sheet
C01.1.
Comment 4d: Final Paving: The road within the ingress/egress easement between Market
Street and Martinsburg Pike must be paved and finished. Not addressed.
Include final pavement or produce agreements assuring completion by others.
Response 4d: The area needing paving and finishing has been highlighted
and a note has been added instructing the contractor to
complete the work. See sheet C01.1.
Comment 9: Agency Approvals: Comment sheets (approvals) are required from the following
agencies: the Frederick County Inspections Department, the Frederick County
Page 2
kimley-horn.com 11400 Commerce Park Drive, Suite 400, Reston, VA 20191 703 674 1300
Fire Marshal, the Virginia Department of Transportation (VDOT), Frederick
County G.I.S., Winchester Airport, Frederick Water, and the Frederick County
Engineer (Public Works).
Response 9: Acknowledged. Approvals are included in this submission
package.
Comment 10: Resubmittal fee: Provide the $500 resubmittal fee for the 3rd submission.
Response 10: Acknowledged. The $500 resubmittal fee is included in this
submission package.
Frederick Water
Comment 1: REPLACE WITH ‘REMOVE GATE VALVE AND INSTALL MJ PLUG IN TEE’
Response 1: The note has been updated to include the above
information. See sheet C02.
Comment 2: LABEL; HP PROTECTUS 3 STAINLESS STEEL FIRE METER AND INCLUDE
DIAMETER
Response 2: The label has been updated to call out the 6” HP Protectus
III Stainless Steel Fire Meter. See sheet C05.
Comment 3: ADD; ‘WITH BOLLARDS’
Response 3: This note has been added. See sheet C05.
Comment 4: MIN. 10’ FW ESMT REQ’D AROUND FH
Response 4: The easement has been updated to 10’. See sheet C05.
Comment 5: ADD; 1”
Response 5: The size has been called out on the plans. See sheet C05.
Comment 6: ALSO STATE DEMANDS IN GPD; DOMESTIC AND IRRIGATION
INDIVIDUALLY
Response 6: A standalone flow model has been provided separately with
the application. Please refer to this document for resolution
of this comment.
Comment 7: Demonstrate that the flow and pressure criteria required by the
FW standards and specifications can be met with the proposed
system. Long form calculations or a digital hydraulic model is
acceptable. Calculations or a summary of model results shall be
sealed by a Professional Engineer licensed in the Commonwealth
of Virginia and submitted under separate cover with the Site Plan.
A brief summary of the model or calculations shall be included in
the Site Plan package but shall not exceed one 24”x36” page in
length. The Frederick Water Engineer will inform the applicant as
to which pages of the model results shall be included on the Site
Plan sheet once the stand-alone report has been deemed
Page 3
kimley-horn.com 11400 Commerce Park Drive, Suite 400, Reston, VA 20191 703 674 1300
acceptable.
Response 7: A standalone flow model has been provided separately with
the application. Pending satisfactory resolution of the flow
model comments, Kimley-Horn with coordinate with
Frederick Water to confirm which sheets from the flow model
to include on the signature set plans.
Comment 8: Water Model submission requirements:
Brief narrative of the project, what is being modeled, and what the
model intends to demonstrate
Standards being evaluated (e.g., fire flow requirement (GPM
based on use), minimum pressure of 20 psi during fire flow).
Anticipated flows for the project including calculations of the
applicable fire flow plus the greater of (a) maximum hour flow or
(b) maximum day flow.
Figures including a vicinity map, project layout, existing Frederick
Water facilities near the project, water model layout with nodes,
pipes, pumps, etc. labled.
Results of the hydrant test that established the boundary
condition for the model or other means of simulating the existing
Frederick Water system.
Pump curve that represents the connection to the existing FW
system.
Table showing all pipes in the model. Attributes shall include pipe
length, diameter, roughness, velocity, etc.
Table showing all nodes in the model. Attributes shall include
assigned flows, elevation, pressure, etc.
Table showing the results of the fire flow analysis including flows
and residual pressures
Response 8: A standalone flow model has been provided separately with
the application. Please refer to this document for resolution
of this comment.
Comment 9: ADD DETAIL THIS SHEET
Response 9: HP Protectus 3 Stainless Steel Fire Meter details have been
added to the plans. See sheet C10.
Sincerely,
Chris Howell, P.E.