RE: Review Comments for Site Plan #40-25 – LRCC Lineman Training Facility
Property Identification Number (PIN): 91-A-99B
First (1st) Submission Comment Responses
Dear Ms. Feltner:
Thank you for the review comments summary letter dated October 7, 2025, regarding LRCC Lineman
Training Facility- Site Plan #40-25. Please see the Timmons Group responses below in italic, numbered
according to the comments provided by each department/agency.
DEPARTMENT OF PLANNING & DEVELOPMENT REVIEW COMMENTS:
1. Master Development Plan. A Master Development Plan is required or a waiver from the Director
of Planning and Development shall be provided. (165-801.03(C)).
Response: A waiver from the MDP has been approved by the Director of Planning and
Development, Wyatt Pearson. Please see the approved waiver on Sheet C1.3.
2. Cover Sheet
a) Reference Number. Add the site plan reference number #40-25.
b) Previous Plan Approvals. Add reference to any other plan or master development plan
approved by the County for the site (§165-802.03(A)(7)). Specify Rezoning (REZ)
applications #04-25 and Site Plans (SP) #32-12.
c) Utilities. Remove Shenandoah Electric from the Electrical Service Provider.
d) FEMA Flood Plain. Indicate whether the parcel is or is not within a FEMA Flood Plain.
Response:
a) The site plan reference number has been added. Please see Sheet C0.0.
b) A list of associated plans and references has been added. Please see Sheet C0.0.
LRCC Lineman Training Facility- Site Plan #40-25
First (1) Submission Comment Responses – Page 2 of 5
CIVIL ENGINEERING | ENVIRONMENTAL | SURVEYING | GIS | LANDSCAPE ARCHITECTURE | CONSTRUCTION SERVICES
c) Shenandoah Electric has been removed from the Electrical Service Provider list. Please see
Sheet C0.0.
d) A note has been added indicating that the parcel is not located within a FEMA Floodplain.
Please see Sheet C0.0.
3. Project Summary
a) FAR. Provide the overall site Floor-Area-Ratio (FAR).
b) Landscaped Area. Provide the required landscaping calculations and the actual
landscaping provided.
Response:
a) The overall site FAR has been provided. Please see the Zoning Table on Sheet C1.2.
b) The required landscaping and actual landscaping area has been provided. Please see the
Zoning Table on Sheet C1.2 as well as landscaping sheets L1.0 – L2.0 for further landscape
analyses.
4. Geometry/Site Layout.
a) Easement. Label and identify all easements on the site plan.
b) Trash Enclosure. All commercial and industrial developments shall be provided with
outdoor trash containers (§165-204.11(D)(2). Such trash container shall not be located in
the front yard areas of such uses. (§165-204.11(D)(3)).
c) Curb & Gutters. Concrete curbing and gutters shall be installed around the perimeter of
all parking lots. All curbing shall be a minimum of six inches in height. All parking lots
shall be included within an approved stormwater management plan. (§165-202.01(D)(3)).
Response:
a) All existing and proposed easements have been labeled on the plans. Please see Sheet C4.0.
b) There is an existing trash enclosure adjacent to the building that will be utilized. It has been
labeled accordingly. Please see Sheet C2.2.
c) Concrete curbing and gutters have been installed around the parking spaces. They are a
minimum of six inches in height and are included in the stormwater management plan. Please
see Sheet C4.0.
5. Landscaping.
a) Zoning Buffer Note. A Category C Buffer is required between HE and RA uses. Identify
the active and inactive portions of the buffer on the landscaping plan.
(§165.203.02(D)(b)). See also proffer statement 2.1 on the required buffer.
LRCC Lineman Training Facility- Site Plan #40-25
First (1) Submission Comment Responses – Page 3 of 5
CIVIL ENGINEERING | ENVIRONMENTAL | SURVEYING | GIS | LANDSCAPE ARCHITECTURE | CONSTRUCTION SERVICES
b) Minimum Landscaped Area. A minimum of 25% of the site shall be green space. (§165-
609.01(D)(13)(b)). Provide the necessary calculations of total site area, impervious area,
and remaining greenspace area.
c) Landscaping; Parking lots. The impervious area of the parking lots shall be provided with
interior and perimeter landscaping.
i. Legend. Provide a legend that identifies the species, caliper, scientific name,
and common name. (§165-802.03(C); §165.202.01(D)(13)).
ii. Perimeter Landscaping. The perimeter of all impervious areas shall be
landscaped with one shade tree for every 2000 square foot of impervious area
for the first 100,000 square feet of the entire site. Provide the necessary
calculation and indicate the required amount of shade trees.
(§165.202.01(D)(13)(a)). Please also refer to the species of shade trees
permitted in §165-203.01(B)(1).
iii. Interior Landscaping. A minimum of 5% of the interior portion of the parking
lot shall be landscaped for the purpose of providing shade trees. Such interior
landscaping shall be provided on raised islands and in continuous raised strips
extending the length of the parking bay. (165.202.01(D)(13)(b)).
iv. Headlight Screening. Headlight screening shall be provided to prevent
headlights from shining into right-of-way or adjacent properties. (§165-
202.01(13)(a)).
Response:
a) Category C buffers have been provided. Please see Sheet L1.0.
b) 85% of the site is green space, thus satisfying the minimum 25% requirement. Please see
Sheet L2.0 for the calculations.
c) Landscaping has been revised to meet the landscaping requirements. Please see Sheets L1.0
and L2.0.
6. Signage. The location, dimensions, and height of all signs shall be shown on the plan (§165-
802.03(C)(17)). Signs shall be in conformance with §165-201.06.
Response: The location, dimensions, and height of all signs have been shown on the plans.
They shall be in conformance with §165-201.06 of the Frederick County Code. Please see
Sheets C1.2, C4.0 and C4.1.
7. Photometric Plan. Provide the proposed height of the parking lot lighting fixtures. Additionally,
a note that includes all statements within Proffer Item #3.1 shall be added to the photometric
plan.
Response: The proposed height of the parking lot lighting fixtures is 20 feet per the pole base
detail on the photometric plan. A note has been added for clarity. A note that includes all
statements within Proffer Item #3.1 have been added to the photometric plan. See Sheet L3.0.
LRCC Lineman Training Facility- Site Plan #40-25
First (1) Submission Comment Responses – Page 4 of 5
CIVIL ENGINEERING | ENVIRONMENTAL | SURVEYING | GIS | LANDSCAPE ARCHITECTURE | CONSTRUCTION SERVICES
8. Agency Approvals. Comment sheets (approvals) are required from the following agencies: the
Frederick County Inspections Department, the Frederick County Fire Marshal, the Virginia a
Department of Transportation (VDOT), Frederick County G.I.S., Frederick Water, Winchester City
Engineering (Julie Carter), Town of Middletown Planning, and the Frederick County Engineer
(Public Works).
Response: Acknowledged. All approved comment sheets have been provided as part of the
submission package.
CITY OF WINCHESTER – UTILITIES REVIEW COMMENTS:
1. Replace 90° waterline bend with 2 - 45° bends and revise profile/easements accordingly.
Response: The 90° waterline bends have been replaced with 2 - 45° bends on all lines. The
plans, profiles and easements have been revised accordingly. Please see Sheets C6.0 and C6.1.
2. Please label the waterline profile as “watermain profile” as opposed to “fire service line profile”.
Response: The profile name has been updated from “fire service line profile” to “watermain
profile”. Please see Sheet C6.1.
3. On the watermain profile, provide 18” separation between the top of the watermain and the
gas, UGT, and UGP crossings.
Response: The watermain profile has been updated to provide 18” separation between the top
of the watermain and the gas, UGT, and UGP crossings. Please see Sheet C6.1.
FREDERICK COUNTY FIRE MARSHAL REVIEW COMMENTS:
1. A No Parking / Fire Lane sign may be required at the new fire hydrant. The additional sign may
be assessed during the Building Final.
Response: A No Parking / Fire Lane has been added behind the proposed fire hydrant. Please
see Sheet C4.1.
FREDERICK COUNTY BUILDING INSPECTIONS REVIEW COMMENTS:
1. All structures shall comply with the current Virginia USBC.
Response: A note has been added per the comment. Please see Note 18 under Site Information
on Sheet C1.1.
LRCC Lineman Training Facility- Site Plan #40-25
First (1) Submission Comment Responses – Page 5 of 5
CIVIL ENGINEERING | ENVIRONMENTAL | SURVEYING | GIS | LANDSCAPE ARCHITECTURE | CONSTRUCTION SERVICES
2. Each structure needs to be permitted independently. This would include all the utility poles
installed for education.
Response: A note has been added per the comment. Please see Note 19 under Site Information
on Sheet C1.1.
3. The structures and site shall comply with the current ICC A117.1 standards.
Response: A note has been added per the comment. Please see Note 20 under Site Information
on Sheet C1.1.
Please contact me directly at (703) 554-6719 or Osvaldo.Ramos@timmons.com with any additional
comments or questions.
Respectfully Submitted,
Timmons Group
Osvaldo Ramos, PE
Project Manager