HomeMy WebLinkAbout2025-09-26 Water Model Summary Report JN 3805 (1)
FREDERICK COUNTY PUBLIC SCHOOLS 4TH HIGH SCHOOL
WATER MODEL SUMMARY REPORT
Located in:
Frederick County, Virginia
Project Number: 3805.0
Date: September 26, 2025
11/10/2025
FREDERICK COUNTY PUBLIC SCHOOLS 4TH HIGH SCHOOL
INTRODUCTION
The following hydraulic analysis report has been prepared by the mechanical plumbing designer
(Stratus) for the project to verify fire suppression sprinkler service for the proposed high
school. Foresight Design Services worked with Patriot Fire and Security to perform fire hydrant
flow / pressure tests to determine the public water system pressures and flows around the project
area. This information is included in the following report.
All that data was then provided to the mechanical / plumbing design team (Stratus) for their use
in building the fire suppression sprinkler hydraulic model. The hydraulic model evaluated the
necessary fire flow demands / pressures against that which was available. As shown in the
attached model print-out, the existing infrastructure has been determined to be adequate to
provide the required flows and pressures for the fire suppression sprinkler system inside the 4th
high school without the need of a fire pump.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 9/9/2025 C:\USERS\MARKULBRICH\DESKTOP\HS4.SDF
JOB TITLE:
WATER SUPPLY ANALYSIS
Static: 90.00 psi Resid: 70.00 psi Flow: 925.0 gpm
-14.7
0.0
20.0
40.0
60.0
80.0
100.0
200300 400 500 600 700 800 900 1000
FLOW (GPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
(2) On Site pressures are based on hose stream deduction at the source
G
A
U
G
E
P
R
E
S
S
U
R
E
(
p
s
i
)
A
C
1
2
B
LEGEND
1 Available pressure
83.59 psi @ 500.2 gpm
2 Required pressure
59.57 psi @ 500.2 gpm
Avail. OnSite Demand Press.
83.59 psi @ 150.2 gpm
Req. OnSite Demand Press.
59.57 psi @ 150.2 gpm
A. Source Supply Curve
B. System Demand Curve
C. Available at Source
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 9/9/2025 C:\USERS\MARKULBRICH\DESKTOP\HS4.SDF
JOB TITLE:
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 90.0 70.0 925.0 83.6 500.2 59.6
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 500.2 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 350.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 150.2 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
B 764.5 - - - - 10.1 - - -
C 764.5 - - - - 13.0 - - -
D 764.5 - - - - 19.4 - - -
E 764.5 - - - - 24.3 - - -
F 735.0 - - - - 38.5 - - -
AV 725.0 - - - - 47.1 - - -
BP1 725.0 - - - - 47.1 - - -
BP2 725.0 - - - - 52.1 - - -
A 764.5 - - - - 9.5 - - -
9 764.5 K= 5.60 11.7 19.1
8 764.5 K= 5.60 10.9 18.5
7 764.5 K= 5.60 9.7 17.4
6 764.5 K= 5.60 9.0 16.8
5 764.5 K= 5.60 8.4 16.2
4 764.5 K= 5.60 7.4 15.3
3 764.5 K= 5.60 8.5 16.3
2 764.5 K= 5.60 7.9 15.7
1 764.5 K= 5.60 7.0 14.8
SOURCE 715.0 SOURCE 59.6 150.2
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 9/9/2025 C:\USERS\MARKULBRICH\DESKTOP\HS4.SDF
JOB TITLE:
NFPA PIPE DATA 5
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 5.60 14.8 Disch 10.00 120 0.9
2 764.5 7.9 0.0 1.000 E: 2.0 2.00 -0.0
1 764.5 7.0 14.8 1.049 12.00 0.075 0.9
Pipe: 2 5.60 15.7 Disch 0.59 120 1.6
A 764.5 9.5 14.8 1.000 T: 5.0 5.00 -0.0
2 764.5 7.9 30.6 1.049 5.59 0.285 1.6
Pipe: 3 5.60 16.3 Disch 9.00 120 1.0
A 764.5 9.5 0.0 1.000 E: 2.0 2.00 -0.0
3 764.5 8.5 16.3 1.049 11.00 0.089 1.0
Pipe: 4 0.0 30.6 2 14.42 120 0.6
B 764.5 10.1 16.3 2.000 T:10.0 10.00 -0.0
A 764.5 9.5 46.9 2.067 24.42 0.023 0.6
Pipe: 5 5.60 15.3 Disch 10.00 120 0.9
5 764.5 8.4 0.0 1.000 E: 2.0 2.00 -0.0
4 764.5 7.4 15.3 1.049 12.00 0.079 0.9
Pipe: 6 5.60 16.2 Disch 0.59 120 1.7
B 764.5 10.1 15.3 1.000 T: 5.0 5.00 -0.0
5 764.5 8.4 31.5 1.049 5.59 0.301 1.7
Pipe: 7 5.60 16.8 Disch 9.00 120 1.0
B 764.5 10.1 0.0 1.000 E: 2.0 2.00 -0.0
6 764.5 9.0 16.8 1.049 11.00 0.094 1.0
Pipe: 8 0.0 31.5 5 14.42 120 3.0
C 764.5 13.0 46.9 A 2.000 2T:20.0 20.00 -0.0
B 764.5 10.1 95.2 2.067 34.42 0.086 3.0
Pipe: 9 5.60 17.4 Disch 10.00 120 1.2
8 764.5 10.9 0.0 1.000 E: 2.0 2.00 -0.0
7 764.5 9.7 17.4 1.049 12.00 0.101 1.2
Pipe: 10 5.60 18.5 Disch 0.59 120 2.1
C 764.5 13.0 17.4 1.000 T: 5.0 5.00 -0.0
8 764.5 10.9 35.9 1.049 5.59 0.383 2.1
Pipe: 11 5.60 19.1 Disch 9.00 120 1.3
C 764.5 13.0 0.0 1.000 E: 2.0 2.00 -0.0
9 764.5 11.7 19.1 1.049 11.00 0.120 1.3
Pipe: 12 0.0 35.9 8 12.17 120 6.4
D 764.5 19.4 95.2 B 2.000 2T:20.0 20.00 -0.0
C 764.5 13.0 150.2 2.067 32.17 0.199 6.4
Pipe: 13 0.0 0.0 14.58 120 4.9
E 764.5 24.3 150.2 C 2.000 T:10.0 10.00 -0.0
D 764.5 19.4 150.2 2.067 24.58 0.199 4.9
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 9/9/2025 C:\USERS\MARKULBRICH\DESKTOP\HS4.SDF
JOB TITLE:
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 14 0.0 0.0 103.89 120 14.2
F 735.0 38.5 150.2 D 4.000 6E:60.0 80.00 12.8
E 764.5 24.3 150.2 4.026 T:20.0 183.89 0.008 1.4
Pipe: 15 0.0 0.0 487.36 120 8.6
AV 725.0 47.1 150.2 E 4.000 4E:40.0 60.00 4.3
F 735.0 38.5 150.2 4.026 T:20.0 547.36 0.008 4.2
Pipe: 16 0.0 0.0 7.00 120 0.0
BP1 725.0 47.1 150.2 F 6.000 A:28.0 28.00 -0.0
AV 725.0 47.1 150.2 6.065 35.00 0.001 0.0
Pipe: 17 0.0 Fixed Pressure Loss Device
BP2 725.0 52.1 150.2 AV 5.0 psi, 150.2 gpm
BP1 725.0 47.1 150.2
Pipe: 18 Source 0.0 3800.00 140 7.4
SOURCE 715.0 59.6 150.2 BP1 6.000 6E111.7 111.72 4.3
BP2 725.0 52.1 150.2 6.065 3911.72 0.001 3.1
NOTES (HASS):
(1) Calculations were performed by the HASS 2023 D computer program
in accordance with NFPA (2020)
under license no. 64640813 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
(2) The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.023 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 14.4 ft/sec at pipe 13.
(4) Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
(5) Fullflow calculations are not done for systems with variable speed pumps.
(6) PIPE FITTINGS TABLE
HASS Pipe Table Name: standard
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 9/9/2025 C:\USERS\MARKULBRICH\DESKTOP\HS4.SDF
JOB TITLE:
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NTee
--------------------------------------------------------
F
F45Ell
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
1.00
2.067 5.00 10.00 3.00 11.00 6.00 1.00 10.00 10.00 10.00
2.50
4.026 10.00 20.00 6.00 22.00 12.00 2.00 20.00 20.00 20.00
5.00
6.065 14.00 30.00 9.00 32.00 10.00 3.00 28.00 28.00 30.00
7.00