HomeMy WebLinkAboutJeff_Craven_Water Model - Utility CalculationsB3150 May 11, 2026 Utility Calculations Frederick County Nichols Junction Townhomes For Engineering Manual Virginia 5/11/2026 Water Model Narrative This water report provides for an analysis for a proposed 36 townhome subdivision, Nichols Junction. To the north and west of the subdivision, there are existing 12 inch water mains that will supply water to the site. Because there are plans for the proposed water lines in Nichols Junction to connect with proposed ones on the neighboring property, Warrior Storage, this analysis includes a connection between the two sites. All pipes were modeled with an estimated friction coefficient of 120. Flowrates with corresponding pressures were provided by Frederick Water and shown below. For simplicity, an estimated equivalent length of pipe was used to determine frictional losses necessary to carry the water from these locations to the site. The primary goal of this analysis was to determine pressure levels at critical points in the water system when supplying the site with needed flre fiow (1250 gpm) and the estimated maximum daily demand for the homes (18.8 gpm) simultaneously. The minimum required pressure for this scenario is 20 psi, and the analysis indicated that the lowest expected pressure on the would be greater than 50 psi. Estimated by 1.6 mi of 8” 120 C-val 750’ elevation Estimated by 1.5 mi of 8” 120 C-val 768’ elevation Walnut Office Estimated by 1.3 mi of 8” 120 C-val 654’ elevation 522S Project 5248 Olde Towne Road Project No. Harrisonburg, VA Subject 540-432-9555 138.6 ft 103.95 ft 46.2 ft 122.43 ft 110.88 ft 46.2 ft 235.62 ft 184.8 ft 46.2 ft Nichols Junction B3150 Flow Calculations 45 psi Qf = Office Hydrant Recorded Flow during test (gpm) Qr =20 psiFlow desired @ Calculated Information 1,912 gpm 1126 gpm 60 psiStatic =Recorded PressuresResidual = Walnut Hydrant Qf =1163 gpm Recorded Flow during test (gpm) Static =53 psi Recorded PressuresResidual =48 psi Recorded PressuresResidual =80 psi Calculated Information Qr =3,222 gpm Flow desired @ 20 psi 522 S Hydrant Calculated Information Qr =3,054 gpm Flow desired @ 20 psi Qf =1501 gpm Recorded Flow during test (gpm) Static =102 psi AVERAGE DAILY WATER AND SEWER DEMAND 10,800 gpd Average Daily Demand (Water) ADD 10,800 gpd PEAKING FACTOR AND FIREFLOW Q = 11.4 * (N^0.544) N =36.0 Q =80.1 MAX hourly domestic demand =P.H. x A.D.D. =80.1 gpm =1.3 gph Required Fire Flow: 1,250 gpm A.D.D. =10800 gpd A.D.D * 2.5 27000 gpd 18.8 gpm 1268.8 gpm SANITARY SEWER HYDRAULIC DESIGN Capacity 8" sanitary pipe at 0.5% slope = 340 gpm (mannings eqn, n value of 0.015) 36 Apartment and Townhouse @ 300 gpd/unit = Max daily domestic demand = = Max daily domestic demand + Needed Fire Flow = = Design flow rate (gpm) Service line size (in) Service line length main to meter (ft)Meter size Check valve size Static Pressure at meter (psi) Residual Pressure at meter (psi) Service line size (in) Service line length meter to bldg (ft) Static Pressure at fixture (psi) Residual Pressure at fixture (psi) 12.0 1 19 5/8 3/4 Inch 75 58.9 1 50 68.5 55.6 Water Service Design Table