HomeMy WebLinkAbout23-25 Review CommentsCOUNTY- of FREDERICK
Department of Planning and Development
540/ 665-5651
Fax: 540/ 665-6395
June 5, 2025
Stuart Little (slittlerwsekivsolutions.com)
Sekiv Solutions, LLC
14207 Pond Chase Place
Midlothian, VA 23113
Re: Review Comments for Site Plan #23-25 — Taco Bell (Route 50 W)
Property Identification Number (PIN): 52-A-F1
Dear Mr. Little:
Planning Staff has reviewed the above -referenced site plan to determine if administrative approval
can be granted. At this time, administrative approval cannot be granted. This site plan cannot be
approved until the issues in this letter, as well as all issues of the other review agencies, have been
adequately addressed. Please review Staffs comments listed below and then prepare a revised site
plan which adequately addresses each concern.
Review Comments:
1) Cover Sheet: The following revisions should be made to sheet C-001:
• Reference Number: Add new site plan reference #23-25.
• Site Data: Note # 4 on legal reference lists an invalid parcel ID. Remove and
replace with correct parcel ID # 52-A-F 1. The Zoning District is listed as Highway
Commercial. This is not a Zoning District in Frederick County. Update to General
Business.
• Site Data: Note # 7 states "utilities: public." This is insufficient. Add the name,
address, and phone number of all utility providers per §165-802.03(A)(10).
Include water and sewer, electric, phone, and internet.
• Site Data: Note # 11 on setbacks is incorrect. There are no side and rear setbacks
in the B2 Zoning District. This is a corner lot with frontage on 2 roads, so there
are 2 fronts. Both fronts have a 35' setback. Correct the minimums in this table
and add dashed building restriction lines on the plan itself (sheet 2 only includes
front setback along Retail Boulevard). Update all subsequent sheets.
• Actual Setbacks: Include the actual setbacks of the building for each side.
• Site Data: Add the name of the Magisterial District the property is located within
(Gainesboro) per §165-802.03(A)(14).
• Site Data: Note # 12 includes the proposed floor area. Add the Floor Area Ratio
(FAR) of the site including the maximum allowed FAR and the proposed FAR
per §165-802.03(B)(1).
• Site Data: Note # 14 regarding parking must be updated. The 5 car stacking spaces
in the drive-thru cannot count towards total required parking. The minimum
stacking distance is 90' per §165-202.01(D)(12). Indicate how many feet of
stacking distance are proposed that meets the 90' minimum. The parking standard
shown is 1 space per 100 SF, which is incorrect. Update the calculations using the
minimum of 1.4 spaces per 100 SF of seating floor area per §165-202.01(A)(1).
107 North Kent Street, Suite 202 • Winchester, Virginia 22601
Re: SP #23-25 — Taco Bell (Route 50 W)
Page 2 of 3
Drive-thru stacking areas cannot count towards the minimum required parking
spaces.
• Zoning Administrator Signature: Add a note that says "site plan valid for five (5)
years from approval date" to the signature block per § 165-802.03(C)(29).
• Previous Rezoning & Proffer Statement: §165-802.03(A)(12) requires reference
to the previous rezoning (REZ #03-03) and inclusion of the proffer statement in
the site plan.
2) Layout & Utility Plan_ The following revisions should be made to sheet C-102:
Zoning: Add the zoning district of all adjoining lots per §165-802.03(C)(1).
Setbacks: Remove the 25' rear yard setback line. There are no side and rear
setbacks in the B2 Zoning District per §165-601.02. Show the 35' front setback
lines for both fronts (the sides abutting Retail Boulevard and Crock Wells Mill
Drive).
Sims: Add the location, dimensions, and height of all signs meeting the
requirements in § 165-201.06.
Pedestrian Access: Safe pedestrian walkways shall be provided to all uses per
§165-202.03(D). Add a pedestrian walkway from the existing sidewalk along
Retail Boulevard to the building entrance.
3) Dumpster Enclosure Details: The following revisions should be made to sheet C-503:
• Dumpster Screening: The rear of the dumpster and the sides are opaque, however
the gate must be opaque as well. Add a note to the site plan that the gate will be
6' tall and completely opaque per § 165-204. 11 (D)(4).
4) Landscape Plan: The following revisions should be made to sheets L-101 & L-102:
Calculations: The perimeter and interior landscaping calculations meeting the
requirements in §165-202.01(D)(13) must be shown.
o Staff Suggestion: Separate the trees and shrubs used to meet ordinance
requirements from those for ornamental purposes. The planting
requirements (species type, minimum caliper/height, and spacing) only
apply to trees and shrubs used to meet the ordinance requirements. Extra
plantings are shown that do not need to meet these requirements. Show
those separately so it is clearer what plantings are used to meet the
ordinance requirements vs. ornamental/supplemental optional plantings.
Minimum Landscaped Area: Show calculations for the minimum landscaped area
of 15% of the lot for the B2 Zoning District and demonstrate where on the site is
counting towards the 15% per §165-601.02.
Trees: Deciduous trees shall be a minimum of one -and -one -quarter -inch caliper
at the time of planting per §165-203.01(B)(2). Revise planting schedule for trees
counting towards the tree requirements.
Headlight Screening: A three -foot -high evergreen hedge, fence, berm, or wall
shall be provided to prevent headlights from shining on public rights -of -way and
adjoining properties per § 165-202.01(D)(13). Headlight screening is required for
the eastern parking spaces facing 52-A-D. Shrubs are used most often. Headlight
screening shrubs must be at minimum three -gallon container and 36" in height at
Re: SP #23-25 — Taco Bell (Route 50 W)
Page 3 of 3
the time of planting spaced four feet on center per §165-203.01(B)(2). Indicate
which shrubs are to be used for headlight screening that meet these requirements.
5) Lighting Plan: The following revisions should be made to sheet LI-101:
• Note: Add a note stating that "All outdoor lighting fixtures shall be designed,
shielded, aimed, located and maintained to shield adjacent properties and to not
produce glare onto adjacent properties or road rights -of -way. Parking lot fixtures
and light fixtures on buildings shall be full -cutoff fixtures" per § 165-201.07(B).
6) Proffer Compliance:
• On Site Development Proffer: Provide elevations of the building on the site plan
meeting material standards outlined in the on -site development proffer. Approval
is needed from the Architectural Control Committee prior to approval of the site
plan. Provide a letter from the Architectural Control Committee stating approval
of the proposed building fagade.
7) Agency Approvals: Comment sheets (approvals) are required from the following
agencies: Building Inspections, Public Works, GIS, Frederick Water, the Fire Marshal,
Virginia Department of Transportation (VDOT), and the Virginia Department of Health.
Additional comments M be provided on subse uent submissions.
After you have revised the site plan, please resubmit one (1) hard copy so that staff may verify the
information contained on the plan addresses the above comments. Staff will also need all the
approved review agency comments. Once the revised hard copy of the site plan has been reviewed,
staff will notify you to submit five (5) copies of the final plan set and a digital (PDF) copy for final
approval. Do not hesitate to contact me should you have any questions or concerns regarding this
letter. Thank you for your consideration.
Sincerely,
Kayla Peloquin/pd
Planner II