HomeMy WebLinkAbout06-19 Middletown Data Center - PIN 90-A-58C - Back Creek - BackfilePlease note: The site plans associated with this file are
located in the file room.
DATE
RECEIVED FROM
ADDRESS Q
FOR
ACCOUNT
HOW PAID
BEGINNING
CASH
BALANCE
Q
CHECK
PAIAMOUNT
O
BALANCE
MONEY
DUE
ORDER
RECEIPT994888
c3 IQ'-). C�
DOLLARS � �
SITE PLAN TRACKING SHEET
Comment Sheets:
GIS
VDOT
Frederick Water
Winchester
Inspections
Stephens City
Public Works
Middletown
Parks & Rec
.port
Health Dept.
Fire
One copy of Site flan application form
Payment of site plan review fee
One reproducible copy of Site Plan
OPEN FILE:
'2� 9 File Opened
a7 Reference Manual updated/number assigned
D-base updated
?� l Scan documents to Planning S: drive
dzlq Application Action Summary updated
Scan additional items as needed (Project Planner to direct)
CLOSE FILE:
S l l Approved (or denied) letter mailed to applicanticopy to file and cc's
File stamped "approved", "denied" or "withdrawn"
Reference Manual updated
119 D-base updated
f l Scanning updated
�Id I Application Action Summary updated
Sys ID #
Pam Deeter
To: Gary Lofton; Rhodes Marston; Greg Unger
Subject: Site Plan approval for Middletown Data Center
Attachments: Approval Ltr - SP#06-19 Middletown Data Center.docx
Good morning,
Please find attached the site plan approval letter from Mr. Klein for Middletown Data Center. If you have any questions,
please contact Mr. Klein.
Pam Deeter,
Secretary II
Dept. Planning & Development
107 N. Kent St. Suite 202
540-665-5651
pdeeter@fcva.us
Pam Deeter
To: Patrick Barker, CEcD; Kenneth Scott
Subject: Site plan approval
Attachments: Approval Ltr - SP#06-19 Middletown Data Center.docx
Good morning,
Please find attached the site plan approval letter from Mr. Klein for Middletown Data Center. If you have any questions,
please contact him.
Pam Deeter,
Secretary II
Dept. Planning & Development
107 N. Kent St. Suite 202
540-665-5651
pdeeter@fcva.us
Pam Deeter
From:
Microsoft Outlook
To:
Rhodes Marston
Sent:
Friday, May 10, 2019 10:10 AM
Subject:
Relayed: Site Plan approval for Middletown Data Center
Delivery to these recipients or groups is complete, but no delivery notification was sent by the
destination server:
Rhodes Marston (jrmmarston(c>gmail.com)
Subject: Site Plan approval for Middletown Data Center
Pam Deeter
From: Microsoft Outlook
To: Gary Lofton
Sent: Friday, May 10, 2019 10:10 AM
Subject: Delivered: Site Plan approval for Middletown Data Center
Your message has been delivered to the following recipients:
Gary Lofton (glofton( fcva.usJ
Subject: Site Plan approval for Middletown Data Center
Pam Deeter
From: Microsoft Outlook
To: Greg Unger
Sent: Friday, May 10, 2019 10:10 AM
Subject: Relayed: Site Plan approval for Middletown Data Center
Delivery to these recipients or groups is complete, but no delivery notification was sent by the
destination server:
Greg Unger (greglunger(&yahoo.com)
Subject: Site Plan approval for Middletown Data Center
Pam Deeter
From: Microsoft Outlook
To: Kenneth Scott
Sent: Friday, May 10, 2019 10:12 AM
Subject: Delivered: Site plan approval
Your message has been delivered to the following recipients:
Kenneth Scott (kscottq fcva.us)
Subject: Site plan approval
Pam Deeter
From: Microsoft Outlook
To: Patrick Barker, CEcD
Sent: Friday, May 10, 2019 10:12 AM
Subject: Delivered: Site plan approval
Your message has been delivered to the following recipients:
Patrick Barker, CEcD (pbarker@yesfrederickva.com)
Subject: Site plan approval
6
0
COUNTY of FREDERICK
May 10, 2019
Eric Duvall, PE
JCL Consulting, LLC
4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
Re: Approval for Site Plan #06-19 Middletown Data Center
Property Identification Number (PIN): 90-A-58C
Dear Mr. Duvall:
Department of Planning and Development
540/ 665-5651
Fax: 540/ 665-6395
The above -referenced site plan was approved on May 9, 2019. The site plan is approved for revisions to
the existing site to alter the parking lot and building outline for the installation of concrete pads for
equipment operation and storage in the M1 (Light Industrial) Zoning District in the Back Creek Magisterial
District.
All requirements of the Frederick County Zoning Ordinance have been met in the approved site plan,
including review agency comments from all relevant review agencies. I am providing you with three (3)
copies of the approved site plan. Please forward these copies to the appropriate representative(s).
Furthermore, advise the owner(s) that a copy should be kept for future reference, and an approved copy
must be kept on the construction site throughout the development process. Once site development is
complete, the owner(s) should contact this office to schedule an on -site inspection. Do not hesitate to
contact me if you have any questions or concerns.
Sincerely,
M. Tyler Klein, AICP
Senior Planner
MTK/pd
Attachments
cc: Gary A. Lofton, Back Creek Magisterial District
J. Rhodes Marston & Greg L. Unger, Back Creek Planning Commissioner
Jane Anderson, Real Estate
Commissioner of Revenue
Patrick Barker, Frederick County Economic Development Authority (email)
Kenneth Scott, Frederick County Fire & Rescue (email)
Middletown Data Center, LLC, 1330 Lynchburg Turnpike, Salem, VA 24153
107 North Kent Street, Suite 202 9 Winchester, Virginia 22601-5000
FOR SITE PLAN COMMENTS
County Department of
I 'Planning & Development
MAY 9 2019 1 t
N Ito:
Frei .County I
DepartRent o£Planriing Development
t107 NorthKert Street:—_
Winchester, Virginia 22601
Phone: (540) 665-5651
Hand deliver to:
Frederick County
Department of Planning & Development
107 North Kent Street, 2°a Floor
Winchester, Virginia 22601
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach two (2) copies of the Site Plan with this sheet.
Applicant's Name: ' JCL Consulting, LLC Telephone: 703-488-9877
Email Address: eduvall@jciconsultingllc.com
Mailing Address: 4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
Name of development and description of the request:
Project Name: Middletown Data Center. Description: Revision to existing site to alter parking lot and building
outline. Site plan also includes the installation of concrete pads for equipment operation and storage.
Location of Property:
8209 Valley Pike, Middletown VA 22645
Department of Planning & Development Comments:
t
Date Received _
Date Reviewed _
Revision Required
i
Signature & Date:
-PLANNING DEPARTMENT USE ONLY -
Review Number 1 2 3 4 5 (circle one)
Date Approved
** Please Return Form to Applicant**
16
•
COUNTY of FREDERICK
Department of Public Works
540/665-5643
FAX: 540/ 678-0682
May 9, 2019
Mr. Eric A. Duvall, PE
JCL Consulting, LLC
4460 Brookfield Corporate Drive
Suite K
Chantilly, Virginia 20151
RE: Revised Site Plan Comments — Middletown Data Center
Dear Mr. Duvall:
Upon review of the revised site plan dated April 17, 2019, we recommend approval of the
subject plan.
�f
Joseph W. Johnson, P.E.
Civil Engineer
JCW/kco
cc: Planning and Development
file
Sincerely,
J06
Joe C. Wilder
Director of Public Works
107 North Kent Street, Second Floor, Suite 200 • Winchester, Virginia 22601-5000
• •
Winch P ster
publi�service-s
Rouss City Hall
15 North Cameron Street
Winchester, VA 22601
04/25/2019
JLC Consulting LLC,
4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
Subject: Utility Comment 2
Dear Mr. Eric Duvall,
Telephone: (540) 667-1815
FAX: (540) 662-3351
TDD: (540) 722-0782
Website: www.winchesterva.gov
The City of Winchester has reviewed the following:
1. Site Plan for Middletown Data Center at 8209 Valley Pike, Middletown VA 22645 (1" Revision)
Based on our review, we have no comments for this site plan.
Sincerely,
Nghi Dam
Utility Engineer I — Public Services
NC
"To provide a safe, vibrant, sustainable community while striving
to constantly improve the quality of fife for our citizens and economic partners. "
Frederick County
Department of Fire and Rescue
Office of the Fire Marshal
1080 Coverstone Drive Winchester, VA 22602
(540) 665-6350 Fax: (540) 678-4739 Email: fmoWcva-us
Plan Review & Comments
Date Received
2/27/2019
Plan/Permit Type Site Plan 02-27-19
Name Middletown Data Center
Address 8209 Valley PIKE
Project Name
Applicant Name & Number
RE#
Permit Number
Middletown
Data Center
JCL Consulting, LLC 703-488.9877
Emergency Vehicle Access: A� ate inadequate N/A
Hydrant Location: �Uate Inadequate N/A
Siamese Location: ate Inadequate NIAXA
Fire Lanes Required: Yes No
Plan Approval Status Approve
Comments
Signature:
Reviewed By: Kenneth Scott, Jr.
n -
Title: �,Zi L1.�
Date Reviewed
3/15/2019
VA 22645
REQUEST FOR SITE PLAN COMMENTS
Frederick County Fire Marshal Comment
Mail to:
Frederick County Fire Marshal
Attn: Fire Marshal
1080 Coverstone Drive
Winchester, Virginia 22602
Hand deliver to:
Public Safety Building
1080 Coverstone Drive
Winchester, Virginia 22602
Phone: (540) 665-6350
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach two (2) copies of the Site Plan with this sheet.
Applicant's Name:
Email Address:
Mailing Address:
JCL Consulting, LLC Telephone: 703-488-9877
eduvallCa-iciconsultingl Ic.com
4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
Name of development and description of the request:
Project Name: Middletown Data Center. Description: Revision to existing site to alter parking lot and building
outline. Site plan also includes the installation of concrete pads for equipment operation and storage.
Location of Property:
8209 Valley Pike, Middletown VA 22645 _ _ _—
Fire Marshal Comments:
-FREDERICK COUNTY FIRE MARSHAL USE ONLY -
Date Received - l 7 Review Number 2 3 4 5 (circle one)
Date Reviewed _
Revision Required Ls- -_ / Date Approved
Signature & Date:
** Please Return Form to Applicant**
RECEIVED
25 FEB 2 7 2019
REQUEST FOR SITE PLAN COMMENTS
City of Winchester Comment
Mail to:
Winchester Planning Department
Attn: Planning Director
15 North Cameron Street
Winchester, Virginia 22601
Hand deliver to:
Rouss City Hall
15 North Cameron Street
Winchester, Virginia 22601
Phone: (540) 667-1815
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach one f 1) copy of the Site Plan with this sheet
Applicant's Name: JCL Consulting, LLC Telephone: 703-488-9877
Email Address: eduvall@jciconsulting[Ic.com
Mailing Address: 4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
Name of development and description of the request:
Project Name: Middletown Data Center. Description• Revision to existing site to alter parking lot and building
outline. Site plan also includes the installation of concrete pads for equipment operation and storage
Location of Property:
8209 Valley Pike, Middletown VA 22645
city
k"
-CITY OF WINCHESTER USE ONLY -
Date Received 3 Review Number 3 4 5 (circle one)
Date Reviewed I
Revision Required Date Approved
Si nature: K Date: ;y
*please eturn Form to Applicant**
42
' RECEIVE
REQUEST FOR SITE PLAN COMMENTS FEB 17 7niq
Frederic Wo
ions
Frederick County Inspections
Department Comment
Mail to:
Frederick County Inspections Department
Attn: Building Official
107 North Kent Street
Winchester, Virginia 22601
Hand deliver to:
Frederick County Inspections Dept.
107 North Kent Street, 2" a Floor
Winchester, Virginia 22601
Phone: (540) 665-5650
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach two (2) conies of the Site Plan with this sheet
Applicant's Name: JCL Consulting, LLC Telephone: 703-488-9877
Email Address: eduvall(cDjciconsultingllc.com
Mailing Address: 4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
Name of development and description of the request:
Project Name: Middletown Data Center. Description: Revision to existing site to alter parking lot and building
outline. Site plan also includes the installation of concrete pads for equipment operation and storage
Location of Property:
8209 Valley Pike, Middletown VA 22645
Department Comments:
-FREDERICK COUNTY INSPECTIONS DEPARTMENT USE ONLY -
Date Received a 1 a--� I l
Date Reviewed 3 -ao I , q
Review Numbe 1J2 3 4 5 (circle one)
Revision Required r j N I Date Approved 3 [ z6 )15
Signature & Date: _y
** F,tease Return Form to Applicant**
18
•
Building shall comply with The Virginia Existing Building Code and Section 304, Business Use Group,
of the Virginia Building Code/2015. Other codes that apply are The Virginia Fire Code 2015, ICC/ ANSI
A117.1-2009 Accessible and Usable Buildings and Facilities and the Virginia Energy Code.
Renovations and additions require asbestos inspection if structure was erected prior to 1985
Building shall maintain height and area as required under T503. Building has full NFPA 13 system
installed. Installation of exterior equipment are equipped with self-contained suppression systems as
required per code. Structural slabs installed to support equipment may require a building permit,
depending on weight and overall design of slab. Please submit slab details for review.
60% of all entrances shall be accessible. Restripe of accessible parking and unloading. Accessible route
provided to main entrance. Van accessible parking spaces shall measure 8' in width with an 8' unloading
area or 11' parking width with a 5' unloading area. Accessible parking signage for van shall include $500
fine. See USBC Section 1106.8 for van signage.
Please note the requirements in Chapter 17 of VBC for special inspection requirements on the type of
structure (Soils, concrete etc.)
S:\Site Ilan comments\2015\Business Middletown Business Centei .doc
•
•
JCL Consulting, LLC
4460 Brookfield Corporate Dr.
Suite K
Chantilly, VA 20151
t()N'11'1TINt I1,C Phone:(703)488-9877
May 9, 2019
M. Tyler Klein, AICP
Department of Planning and Development
107 North Kent Street, Suite 202
Winchester, VA 22601-5000
Re: Plan Number: SP# 06-19
Plan Name: Middletown Data Center (PIN: 90-A-58C)
Dear Mr. Klein,
The following are the responses to the comments dated April 18, 2019 on the above referenced project:
FREDERICK COUNTY REVIEW COMMENTS:
Comment 1: Security Fencing: Comment not addressed. Notes and details (i.e. type, height) regarding the
proposed security fencing should be provided and clearly depicted and labeled. Renderings of
the proposed gate(s) should also be provided on the plan set.
Response: Security fence and gate typical details are provided. See sheet 3.
Comment 2: Agency Approvals. Staff acknowledges agency review comments are forthcoming. The designer
should ensure review agency comments from the "City of Winchester' are from the City Engineer
as the site is served by City water/sewer. Comments are not required from the City's Planning
Department.
Response: Acknowledged. Agency approvals are attached.
Comment 3: Parking: On Sheet 2 update the number of parking spaces remaining from 59 to 49 (as counted
on Sheet 4); add a note that 80 spaces are being removed as part of this project.
Response: Parking tabulation is updated. Note is provided in parking tabulation. See sheet 2.
Comment 4: Building Restriction Lines: Update the BRL and label on sheet 5 from the "Access Road," owned
by the Board of Supervisors, to 75-feet, as required for front setbacks in the M1 zoning district.
Response: BRL of 75-feet is provided. See sheet 4 & 5.
Comment 5: Landscape Plan: The referenced "See Landscape Plan for Tree Removal" (Sheet 4) should be
provided for staff to ensure the number of required trees (62) is still being met. If any trees are
being removed, this should be reflected in the calculations/notes provided (i.e. how many trees
are required, how many are currently on site, how many are being removed, and what is the
remaining total post -development) on Sheet 2. Staff may provide additional comments after
review of the submitted Landscape Plan.
Response: Landscaping calculation is provided in sheet 2. Proposed tree location is shown on site plan,
see sheet 5. A landscaping plant schedule is provided in sheet 3.
Please feel free to contact me at 703-488-9877 should you have any questions. Thank you.
Sincerely,
JCL CONSULTING, LLLCC
(�Q.G!'i Z/)U.,aJ
Eric Duvall, P.E.
Tyler Klein
From: Tyler Klein
Sent: Thursday, April 18, 2019 2:S9 PM
To: Eric Duvall
Subject: SP #06-19 - Middletown Data Center; additional review comments
Eric, staff has reviewed the resubmission of the above site plan. Staff offers the following additional comments:
Outstanding Comments from 1st Submission
Security Fencing: Comment not addressed. Notes and details (i.e. type, height) regarding the proposed security fencing
should be provided and clearly depicted and labeled. Renderings of the proposed gate(s) should also be provided on the plan
set.
• Agency Comments: Staff acknowledges agency review comments are forthcoming. The designer should ensure review
agency comments from the "City of Winchester" are from the City Engineer as the site is served by City water/sewer.
Comments are not required from the City's Planning Department.
Additional Comments on 2°d Submission:
• Parking: On Sheet 2 update the number of parking spaces remaining from 59 to 49 (as counted on Sheet 4); add a note that
80 spaces are being removed as part of this project.
• Building Restriction Lines: Update the BRL and label on sheet 5 from the "Access Road," owned by the Board of
Supervisors, to 75-feet, as required for front setbacks in the M1 zoning district.
• Landscape Plan: The referenced "See Landscape Plan for Tree Removal" (Sheet 4) should be provided for staff to ensure
the number of required trees (62) is still being met. If any trees are being removed, this should be reflected in the
calculations/notes provided (i.e. how many trees are required, how many are currently on site, how many are being removed,
and what is the remaining total post -development) on Sheet 2. Staff may provide additional comments after review of the
submitted Landscape Plan.
Please resubmit one (1) copy of the revised plan set to ensure the above comments are addressed, along with any review agency
comments/approvals. Should you have any additional questions, please let me know.
M. Tyler Klein, AICP
Senior Planner
Department of Planning & Development
Frederick County, Virginia
107 N. Kent Street
Winchester, VA 22601
(540)722-8248
tklein .fcva.us
CONSULTING. LLC
April 17, 2019
M. Tyler Klein, AICP
Senior Planner
•
JCL Consulting, LLC
4460 Brookfield Corporate Dr.
Suite K
Chantilly, VA 20151
Phone: (703) 488 9877
Department of Planning and Development
107 North Kent Street, Suite 202
Winchester, VA 22601-5000
Re: Plan Number: SP# 06-19
Plan Name: Middletown Data Center (PIN: 90-A-58C)
Dear Mr. Klein,
•
The following are the responses to the comments dated February 28, 2019 on the above referenced project:
FREDERICK COUNTY REVIEW COMMENTS:
Comment 1: Site Plan Reference. Add the site plan number, SP# 06-19, to the plan set.
Response: Site plan number has been added to the plan set. See sheet 1.
Comment 2: General Notes: Notes #2 and #3 on Sheet 1 do not appear to be related to this project and should
be removed/amended. Frederick County GIS records do not indicate a floodplain in the vicinity of
or within the project site. The County's 2035 Comprehensive Policy Plan denotes the project site
as outside of the County's Urban Development Area (UDA) and the future land use plan denotes
this site as part of the "Rural Areas."
On Sheet 2, General Notes, "Open Space Required" should be revised to "industrial use- 25%" as
specified in 16S-601.02. The "Floodplain" notes under "Environmental Features" should be
removed, see comment above.
Response: Notes have been updated. See sheet 1. General Notes, "Open Space Required" has been
revised to industrial use-25%. See sheet 2.
Comment 3: Previous Plan Approvals. Previous site plan approvals should be noted on the plan set, including
Site Plans (SP) #13-84, #43-98, #25-15 and #47-16.
Response: Previous plan approvals note has been added. See sheet 1.
Comment 4: Signage. Add a not specifying that all signage will conform to the requirements of the Frederick
County Zoning Ordinance. As applicable, add a note to the plan set that no signage is proposed
(or modified).
Response: Signage note has been provided. See sheet 2.
Comment 5: Securing Fencing. Note and add details of any new fencing (i.e. chain link) as applicable. Staff
acknowledges notes regarding fencing to -be -eliminated, but it is not clear on the sheet 5 where,
if any, new fencing is proposed.
Response: Security fence has been updated. See sheet 5.
Comment 6: Agency Approvals. Review agency comment sheets are required from the following agencies: the
Frederick County Inspections Department, the Frederick County Fire Marshall, the Frederick
County Engineer (Public Works), and the City of Winchester.
Response: Acknowledged.
•
0
Please feel free to contact me at 703-488-9877 should you have any questions. Thank you.
Sincerely
JCL CQNIALTING, LLC
Eric Duvbll, P.E.
Director bkngineering
COUNTY of FREDERICK
Department of Planning and Development
540/ 665-5651
Fax: 540/ 665-6395
February 28, 2019
Eric Duvall, PE
JCL Consulting, LLC
4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
Re: Review Comments for Site Plan #06-19 Middletown Data Center
Property Identification Number (PIN): 90-A-58C
Dear Mr. Duvall:
Planning Staff has reviewed the above -referenced site plan to determine if administrative approval
can be granted. At this time, administrative approval cannot be granted. This site plan cannot be
approved until the issues in this letter, as well as all issues of the other review agencies, have been
adequately addressed. Please review Staff's comments listed below and then prepare a revised site
plan which adequately addresses each concern.
Review Comments:
1) Site Plan Reference. Add the site plan number, SP# 06-19, to the plan set.
2) General Notes: Notes #2 and #3 on Sheet 1 do not appear to be related to this project and
should be removed/amended. Frederick County GIS records do not indicate a floodplain in
the vicinity of or within the project site. The County's 2035 Comprehensive Policy Plan
denotes the project site as outside of the County's Urban Development Area (UDA) and
the future land use plan denotes this site as part of the "Rural Areas."
On Sheet 2, General Notes, "Open Space Required" should be revised to "industrial use —
25%" as specified in § 165-601.02. The "Floodplain" notes under "Environmental
Features" should be removed, see comment above.
3) Previous Plan Approvals. Previous site plan approvals should be noted on the plan set,
including Site Plans (SP) #13-84, #43-98, #25-15 and #47-16.
4) Signage. Add a note specifying that all signage will conform to the requirements of the
Frederick County Zoning Ordinance. As applicable, add a note to the plan set that no
signage is proposed (or modified).
5) Securing Fencing. Note and add details of any new fencing (i.e. chain link) as applicable.
Staff acknowledges notes regarding fencing to -be -eliminated, but it is not clear on the
Sheet 5 where, if any, new fencing is proposed.
6) Aaenev Approvals. Review agency comment sheets are required from the following
agencies: the Frederick County Inspections Department, the Frederick County Fire
Marshall, the Frederick County Engineer (Public Works), and the City of Winchester.
107 North Kent Street, Suite 202 9 Winchester, Virginia 22601-5000
Review Comments — SP #06-19 Middletown Data Center
February 28, 2019
Page 2 of 2
After you have revised the site plan, please resubmit one copy so that Staff may verify the
information contained on the plan addresses the above comments. Staff will also need all approved
review agency comment sheets, at least five (5) copies of the final plan set and a digital (PDF) copy
for approval.
Do not hesitate to contact me if you have any questions or concerns regarding this letter.
Sincerely,
M. Tyler Klein, AICP
Senior Planner
MTK/pd
Attachment
cc: Middletown Data Center, LLC, 1330 Lynchburg Turnpike, Salem, VA 24153
0
Pam Deeter
To: eduvall@jciconsulting.com
Subject: Middletown Data Center
Attachments: Review Comments - #06-19 Middletown Data Center.docx
Good afternoon,
Please find attached the review for comments letter from Mr. Klein for the project Middletown Data Center. If you have
any questions, please contact Mr. Klein.
Pam Deeter,
Secretary II
Dept. Planning & Development
107 N. Kent St. Suite 202
540-665-5651
pdeeter@fcva.us
SITE PLAN APPLICATION
/�Office Use Ortly-
Date Application Received: o-n (Q /1 AppClication #: ( )�o'lq
Fees Received: 031 M O' Receipt #: Q Q g 8 d y Initials: ro
1.
2. -
Project Title: Middletown Data Center ,
Project Description: Site plan revising parking lot layout and building outline. Site will include installation
of concrete pads for equipment operation and storage.
3.
Location of Property: 8209 Valley Pike, Middletown VA 22645
(Street address)'
4.
Applicant/Designer:
Name: JCL Consulting, LLC
Telephone: 703-488-9877
Primary Point of Contact: Eric Duvall
email: eduvall@jciconsultingllc.com
Address: 4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
5.
Property Owner (if different than above):
I
Name: Middletown Data Center, LLC
,
Telephone: 804-787-0867
i
Address: 1330 Lynchburg Turnpike
'
Salem, VA 24153
1
6.
Property Information:
a. Property Identification Number:
90-A-58C
b. Total acreage of the parcel to be developed:
6.15 acres
c. Total disturbed area of the parcel:
2.06 acres
i
d. Present Use:
Data Center w/ communication dish
e. Proposed Use:
Data Center w/ communication dish
f. Magisterial District(s)
Back Creek.
i r
II 8
0
a
r
7. Site Plan Type:
a. Is this an original or new site plan? Yes II
No
b. Is this a revised site plan? Yes
No
If yes provide all previous site plan numbers:
C. Is this a minor site plan? Yes Ll_
No
If yes provide all previous site plan numbers:
8. Zoning Information:
a. Current Zoning:
M-1 Light
Industrial
b. Was this property Rezoned? Yes
F
No
c. If yes provide the rezoning number for this property:
N/A
_
d. Are there any proffers for this property? Yes
No
X
e. Has a MDP been approved for this property? YesH
No
X
f. If yes provide the MDP number for this property: N/A
9. Adjoining property zoning and use:
USE
North
Vacant
East
Industrial
South
Interstate 81
West
Industrial
ZONING
M-1
M-1
M-1
I have read the material included in this package and understand what is required by the Frederick County Planning
Department. I also derstand that all required material will be complete prior to the submission of my site plan.
Signature:
Name (Printed): Eric Duvall
Date: 2/21 /2019
7
Special Limited Power of Attorney
County of Frederick, Virginia
Frederick Planning Website: www.fcva.us
Department of Planning & Development, County of Frederick, Virginia
107 North Kent Street, Winchester, Virginia 22601
Phone (540) 665-5651 Facsimile (540) 665-6395
Know All Men By These Presents: That I (We)
(Name)
Middletown Data Center, LLC
(Address) 1330 Lynchburg Turnpike, Salem VA 24153
(Phone)
the owner(s) of all those tracts or parcels of land ("Property") conveyed to me (us), by deed recorded in the
Clerk's Office of the Circuit Court of the County of Frederick, Virginia, by
Instrument No. 18 0010765
on Page
Parcel: 90 Lot: 58C Block: Section:
do hereby make, constitute and appoint:
and is described as
Subdivision:
(Name) JCL Consulting, LLC (Phone)
703-488-9877
(Address) 4460 Brookfield Corporate Drive, Suite K, Chantilly, VA 20151
To act as my true and lawful attorney -in -fact for and in my (our) name, place and stead with full power and
authority I (we) would have if acting personally to file planning applications for my (our) above described
Property, including:
Rezoning (including proffers)
_Conditional Use Permit
_Master Development Plan (Preliminary and Final)
Subdivision
Site Plan
_Variance or Appeal
My attorney -in -fact shall have the authority to offer proffered conditions and to make amendments to previously
approved proffered conditions except as follows:
NOT APPLICABLE
This authorization shall expire one year from the day it is signed, or until it is otherw' a rescinded or modified.
In witness thereof, I ( e) have hereto set my (our) hand and seal this day of a, _, 20�
/ / /l1, ii
Signature(s) 4 � --
State of Virginia, City/County of , To -wit:
I, ,�(� am N�kJAJL a Notary Public in and for the jurisdiction aforesaid,
certify that the person(s) who signed to the foregoing instrument personall appeared before me and has
cknowledged the,same before mein the jurisdiction aforesaid this95 day o WAIWu 0 1 q .
l A 41', lv�— �t— My Commission Expires: ",-L 30
Notary Public 0-o �
REQUEST FOR SITE PLAN COMMENTS
Frederick County Department of
Planning & Development
Mail to:
Frederick County
Department of Planning & Development
107 North Kent Street
Winchester, Virginia 22601
Phone: (540) 665-5651
Hand deliver to:
Frederick County
Department of Planning & Development
107 North Kent Street, 2°d Floor
.Winchester, Virginia 22601
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach two (2) conies of the Site Plan with this sheet.
Applicant's Name.
Email Address:
Mailing Address:
JCL Consulting, LLC Telephone: 703-488-9877
eduvall@jciconsultinglic.com
4460 Brookfield Corporate Drive, Suite K
Chantilly, VA 20151
I
Name of development and description of the request:
Project Name: Middletown Data Center. Description: Revision to existing site to alter parking lot and building
outline. Site plan also includes the installation of concrete pads for equipment operation and storage.
Location of Property:
8209 Valley Pike, Middletown VA 22645
i
i
Department of Planning & Development Comments:
i
Date Received _
Date Reviewed _
Revision Required
Signature & Date:
-PLANNING DEPARTMENT USE ONLY -
Review Number 1 2 3 4 5 (circle one)
Date Approved
** Please Return Form to Applicant**
16
4
SITE PLAN APPLICATION CHECKLIST
The checklist shown below specifies the information which is required to be submitted as part of the site
plan application. The Department of Planning & Development will review the application to ensure that
it is complete prior to accepting it. If any portion of the application is not complete, it will be returned to
the applicant(s).
Fx�]— (1) One (1) set of approved comment sheets are required from each relevant
review agency prior to final approval of a site plan. It is recommended that
applicants contact the Department of Planning & Development to determine
which review agencies are relevant to their site plan application. A list of
potentially relevant review agencies is shown below:
FFrederick County Department of Planning & Development
ElVirginia Department of Transportation (VDOT)
N/� Department of GIS (Geographic Information Services)
EFrederick Water
Frederick County Building Inspections Department
Frederick County Department of Public Works
Frederick County Fire Marshal
NVirginia Department of Health
N� Frederick County Department of Parks & Recreation
N� City of Winchester
N� Town of Stephens City
N/ Town of Middletown
N Winchester Regional Airport Authority
N� Frederick County Public Schools (for residential plans)
(2)
One (1) copy of the Site Plan application form.
❑X
(3)
Payment of the site plan review fee.
x(4)
Two (2) copies of the site plan for review.
(5)
Completed Special Limited Power of Attorney (original).
N�
(6)
Traffic Impact Analysis (if applicable).
10
i
SITE PLAN CHECKLIST
The Site Plan Checklist, shown below, lists the information which is required to be on each site plan. Site plans
which are incomplete or missing information will be returned to the applicant (s) for revision.
Project Information Section
SHEET 1
(1)
A title that includes the name of the proposed or existing business and a subtitle which
describes the proposed development.
X SHEET 1
(2)
The name, address, and phone number of the land owner, developer, and designer.
X SHEET 1
(3)
The Frederick County Property Identification Number (PIN) of all lots included on the
site plan.
X N/A
(4)
The number and type of dwelling units included on the site plan for residential uses.
X SHEET 1
(5)
The total land area and total developed land area of all lots included on the site plan.
X SHEET 2
(6)
A detailed description of the proposed use or uses of the development, as well as a
description of the existing use or uses.
__D/A
(7)
A reference to any other site plan, master development plan approved by the county
for the site.
X SHEET 1
(8)
The date the site plan was prepared and a list of all revisions made, including the date
and a description of why the site plan was revised.
X SHEET 1
(9)
A table of contents including all pages of the site plan.
FIS H E ET 1
(10)
A list of all proposed utility providers, with their address and phone number.
X SHEET 1
(11)
A location map showing the location of the site, along with the location of streets,
roads and land uses within five hundred (500) feet of the property.
X N/A
(12)
A statement listing all requirements and conditions placed on the land included in the
site plan resulting from approval of conditional zoning or a conditional use permit.
X SHEET 2
(13)
A description of setbacks or conditions placed on the site as a result of an approved
variance.
X SHEET 1
(14)
The name of the Magisterial District the property is located within.
Calculations Section
X SHEET 1 (15) Calculations showing the Floor Area Ration (FAR) of the site, including the maximum
allowed FAR, total ground floor area, total floor area, and total lot area.
X SHEET 2 (16) Calculations showing the total number of required and proposed parking spaces,
11
0
including the total number of existing and proposed spaces.
SHEET 2 (17) Calculations showing the total number of required handicap spaces, including the total
number of existing and proposed spaces.
X SHEET 2 (18) Calculations showing the total number of required loading spaces, including the total
number of existing and proposed spaces.
X I SHEET 2 (19) Calculations showing the total number of required perimeter and interior trees
required, including the number of provided trees.
X SHEET 2 (20) Calculations showing the percentage of the property that will be landscaped and the
percentage of woodlands disturbed.
X SHEET 2 (19) Calculations showing the total number of required perimeter and interior trees
required, including the number of provided trees.
Site Plan & Details Section
X SHEET 4 (21) The location of all adjoining lots with the owner's name, specific use, zoning, and
zoning boundaries shown.
X SHEET 4/5 (77) The location of all existing or planned right-of-ways and easements that are located on
or adjoin the property, with street names, widths, and speed limits shown.
-X SHEET 4/5 (23) All nearby entrances that are within two hundred (200) feet of any existing or
proposed entrances to the site.
X SHEET 4/5 (24) All existing and proposed driveways, parking and loading spaces, parking lots and a
description of surfacing material and construction details to be used. The size and
angle of parking spaces, aisles, maneuvering areas, and loading spaces shall be shown.
EI ALL
(25)
A North arrow.
X ALL
(26)
A graphic scale and statement of scale.
EIALL—
(27)
A legend describing all symbols and other features that need description.
X SHEET
(28)
A boundary survey of the entire parcel and all lots included with distances described at
least to the nearest hundredth of a foot.
X SHEET 4
(29)
The present zoning of all portions of the site, with the location of zoning boundaries.
X SHEET 4/5
(30)
The location of all existing and proposed structures, with the height, specific use,
ground floor area, and total floor area labeled.
-ES H E ET 4/5
(31)
The location of all existing and proposed outdoor uses, with the height, specific use,
and land area labeled.
X SHEET 4/5
(32)
Existing topographic contour lines at intervals acceptable to the Zoning Administrator.
Proposed finished grades shall be shown by contour.
12
I
0 6
X SHEET 4/5 33 The location of the front, side, and rear yard setback lines required by the applicable
zoning district.
X SHEET 2 (34) The location and boundaries of existing environmental features, including streams,
floodplains, lakes and ponds, wetlands, natural stormwater retention areas, steep
slopes, and woodlands.
X SHEET 2
(35)
The location of outdoor trash receptacles with details for all required screening
elements.
X SHEET 2
(36)
A Photometric Plan per §165-201.07.
X SHEET 12
(37)
The location, dimensions, and height of all signs.
X SHEET 2
(38)
The location of required buffers, landscaping buffers, and landscaped screens,
including examples, typical cross sections or diagrams of screening to be used. The
location and dimensions of required fencing, berms, and similar features shall be
specified.
X SHEET 2
(39)
The location of recreational areas and common open space.
X SHEET 2
(40)
The location of all proposed landscaping with a legend. The caliper, scientific name,
and common name of all deciduous trees. The height at planting, scientific name, and
common name of all evergreen trees and shrubs.
X SHEET 2
(41)
The height at planting, caliper, scientific name, and common name shall be provided
for all proposed trees. The height at planting, scientific name and common name shall
be provided for all shrubs.
X N/A
(42)
The location of sidewalks and walkways, including all sidewalks or bicycle paths
required along any road right of way.
X I NIA
(43)
The location and width of proposed easements and dedications.
F11 SHEET 14-1
�44)
A stormwater management plan describing the location of all stormwater management
facilities with design calculations and details.
X SHEET 7-10(45)
A soil erosion and sedimentation plan describing methods to be used.
X SHEET 4,5,1(146)
The location and size of sewer and water mains and laterals serving the site.
13
0
6
X SHEET 13 (47) Facilities necessary to meet the requirements of the Fire Code.
ALL (48) A signed seal of the certified Virginia land surveyor, architect, or engineer who
prepared the plan. The seal and signature of the engineer, surveyor or architect shall
be on each sheet of the site plan.
SHEET 1 (49) A space labeled "Approved by the Frederick County Zoning Administrator" for the
signature of the Zoning Administrator, approval date, and a statement that reads "site
plan valid for five (5) years from approval date."
FISHEET 2 (50) All requirements specified elsewhere in the County Code, including but not limited to
the Subdivision Ordinance.
14
-Ncument Appr0v,7a1 Forte
PLEASE REVIEW THE ATTACHED UOC
YOUR APFRO VAL PLEASE I7aIT �' IF T &DOCUI�'T Jt�EET, A1l'D PROE TFfE DATE ANDTTIvlE OF
YOUR APPROVAL.
PaifiaPs Hat- e
Candice
i
Hark
Dave
Tiler f'Y77Z
—�� Z Z 7 %
1�tilte
Join
COMMENTS:
Received by Clerical Stgff(Date & Time);
a a77 1 g
(S.01rce on StsekbortFormfU70cument Approvs! Form _61712016)
JCL Consulting, LLC
4460 Brookfield Corporate Dr.
Suite K
Chantilly, VA 20151
CONSULTING, LLC Phone: (703) 488-9877
LETTER OF TRANSMITTAL
U FEB 2 7 2019
F.'1FD:-R1CK-C:0U`!TY
To: Frederick County Government
Dept. of Planning and Development
107 North Kent Street
Winchester, VA 22601
Date: February 27, 2019
Project Name: Middletown Data Center
Project Number: 0073-A-001
Re: Site Plan —1s` Submission
Attn: Tyler Klein
We Are Forwarding The Following Items:
❑ Originals ❑ Rcproducibles X Prints ❑ Copy of Letter
❑ Shop Drawings
❑ Specifications ❑ Other:
Qty.
Description
2
Site plan —1st submission
1
Site plan Application
1
Site plan checklist
1
Check for $3,100 $200 per 2.06 acres rounded up plus 2,500 base fee