HomeMy WebLinkAbout18-16 CommentsRECEIVED 1.,0 12 2016
REQUEST FOR SITE PLAN COMMENTS
Frederick County Fire Marshal Comment
Mail to:
Frederick County Fire Marshal
Attn: Fire Marshal
1800 Coverstone Drive
Winchester, Virginia 22602
Hand deliver to:
Public Safety Building?
1800 Coverstone Drive
Winchester, Virginia 22602
Phone: (540) 665-6350
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach two (2) copies of the Site Plan with this sheet.
Applicant's Name: Tim Stowe Telephone: 540.686.7373
Mall Ing Address: Stowe Engineering - 103 Heath Court
Winchester, VA 22602
email: timstowe@stowecompanies.com
Name of development and/or description of the request:
Miller Milling boiler room addition
Location of Property:
Miller Milling, 302 Park Center Drive, Winchester, VA 22603
Fire Marshal Comments:
-FREDERICK G'OUNTV FIRE MARSHAL USE ONLY -
Date Received 5(I�e 1 b Review Number 2 1 4 5 (circle one)
Date Reviewed 5 14�l 1(0
Revision Required o Date Approved '' S /�-C
Si -nature &Date_ v Slro !t>
** Please Return Form to Applicant**
20
Frederick County
Department of Fire and Rescue
Office of'the Fire Marshal
1080 Coverstone Drive 11 inckester, V4 22602
(540) 665-6350 Fax: (540) 678-4739 Entail. finn�dJcva,us
Plea Review & Comments
t
Date Received Date Reviewed
5/12/2016 5/16/2016
Plan/Permit Type Minor Site Plan 05-12-16
Name Miller Milling Company
Address 302 Park Center Winchester VA 22603
Project Name Boiler Room Addition
Applicant Name & Number Stowe Engineering 540-686-7373
RE#
Permit Number
Emergency Vehicle Access:
A eq ate Inadequate
N/A
Hydrant Location:
�)ute Inadequate
N/A
Siamese Location:
Adequate Inadequateq
Fire Lanes Required:
Yes No
N/A
Plan Approval Status
Approve
Comments
Signatun�
Reviewed By: Kenneth Scott, Jr.
Title: -�
REQUEST FOR SITE PIAN COMMENTS
Frederick County :Inspections
Department Comment
Mail to:
Frederick County Inspections Department
Attn: Building Official
107 North Kent Street,
Winchester, Virginia 22601
Land deliver to:
Frederick County Inspections Dept.
107 North Kent Street, 2nd Floor
Winchester, Virginia 22601
Phone: (540) 665-5650
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach two (2) copies of the Site Plan with this sheet
Applicant's Name: Tim Stowe
Mailing Address: Stowe Engineering - 103 Heath Court
Winchester, VA 22602
email: timstowe@stowecompanies.com
Telephone: 540.686.7373
SUOQDD , s-Ul ? -br;� 71jGr1�i
Name of development and/or description of the request: Aluno7
Miller Milling boiler room addition
c-•
Location of Property:
Miller Milling, 302 Park Center Drive, Winchester, VA 22603
Inspe tions Department Comments: /
rYXJlrt'lpi✓!,�-S C1iLf, ��- �1-i7� h/,c �-a:
-FREDERICK COUNTY INSPECTIONS DEPARTMENT USE ONLY -
Date Received )2 i (o Review Number 1 2 3 4 5 (circle one)
Date Reviewed Lp
Revision Required bin to Approved
Signature & Date: 5,125'%1,.
�� ** Please Return Form to Applicant"
18
Buildings shall comply with The Virginia Uniform Statewide Building Code, Section 307 — High
Hazard Use Group of the International Building Code/2012. Other Code that applies are the
International Energy Code, ICC/ANSI Al 17.1-09 Accessible and Usable Buildings and
Facilities and Virginia Rehabilitation Code. Design plans submitted for permit application shall
be sealed by a Virginia Licensed Design Professional. Occupant load and fire egress plans shall
be indicated on sealed plans at time of submittal.
Proposed 450 sq ft boiler addition shall meet height and area for the type of construction as
allowed in T503 with applicable increases. Also, addition shall conform to the construction
requirements of the main building (High Hazard). Alterations shall not interfer with the original
design of the facililty. An evaluation of the explosion design may need to be evaluated.
Building will require a full NFPA 13 system as required for H -Hazardous Use. Boiler room shall
be separated as required for incidental use as required.
All required egress shall meet ANSI A117.1-09 for slopes.
Processing equipment that handles hazardous material is not exempt from permitting per Section
102.3 of the USBC
All required egress shall be accessible and meet ANSI Al 17-1.12 for slopes.
The travel distance to the nearest restroom facility shall not exceed 500' travel distance unless
approved by the Authority having Jurisdiction.
Please note the requirements in Chapter 17 of IBC for special inspection requirements on the
type of structure.( Soils, concrete etc..).