HomeMy WebLinkAbout07-16 CommentsRE QUEST FOR SITE PLAN COMMSENTS
Fi-edericif. County Inspections
D-op-artment "Coln snent-
Mail to:
Frederick County Inspections Department
Attn: Building Official
107 North Kent Street,
Winchester, Virginia 22601
Hand deliver to:
Frederick County Inspections Dept.
107 Norih Ken i Street, 2nd Floor
Winchester, Virginia 22601
Phone: (540) 665-5650
Applican0 It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach tLv—ofD codes of the Site Plan with this sheet.
Applicant's Name: George Stick -man
Mailing Address: Howatc! Shockey & Sons, Inc.
P.O. Box 2530
Winchester, VA 22604
Name of development and/or description of the request:
Kingspan insulation –Manufacturing Facility Building & Renovations
Location of Property:
Kingspan Insulation, LLC
172 Pac& My
Winchester, VA 22603
Inspections Department Comments:
Telephone: 540-723-4133
----- - --- -------- .......... ......... ....... ...... . - ----- - -- . ..... .... ---
n—ILEDERICY. COUNTIT Iii PECTIOILS DEP< RVA-,'ENTT USE 4J-NLV-
mate llLeceived i jt Review Nimaber 1 2 3 4 5 (circle one)
Date Kr Yjewed
Revision Required Date Approved
Signature & Date:
Please fir ,,�orr- Fovw to Apip1h7aut—',
M
Addition to existing Factory use group shall comply with The 2012 Virginia Uniform Statewide
Building Code and Section 306 — F. -Factory Use Group. Other Code that applies is ICC/ANSI
A117.1-09 Accessible and Usable Buildings and Facilities, 2012 Virginia Energy Code.
Structural plans and plans submitted for permits for the building project shall be sealed by a
Virginia Licensed Design Professional.
Addition shall comply with section 507 for unlimited area. Unlimited area buildings require
open perimeter of 60'. Building or structures within the 60' shall comply with all the
requirements of the main structure. Fire Pump room within 20' is fully sprinklered and will be
required to comply with the requirements for the unlimited area facility.
Two existing tanks located on site plan. The distance to new structure and existing structure to
existing tanks shall comply with NFPA requirernents.
Exits located on site and appear to meet ANSI for accessibility
Please note the requirements in Chapter 17 of the IBC for special inspections for this type of
st.ructure.(soil, concrete, bolts, etc.)
s:\site plan comments12012\f.'actory, kingsspan addition..doc
Date Received
2/29/2016
Frederick County
Department of Fire and Fescue
Office of the Fire Marshal
1080 Coverstone Drive Winchester, VA 22602
(540) 665-6350 Fax: (540) 678-4739 Einai1. fnro(a), fcva. us
Plan Review & Cornmento,
Plan/Permit Type Site Plan 2/29/16
Name Kingspan North America
Address 172 Pactiv WAY Winchester
Project Name Manufacturing Building & Renovations
Applicant Name & Number Howard Shockey & Sons 540-723-4133
RE#
Permit Number
Emergency Vehicle Access:
Hydrant Location:
Siamese Location:
Fire Lanes Required:
Plan Approval Status
Comments
Signature_L_
Reviewed By: Kenneth Scott, Jr.
Title:
A ! uOte Inadequate N/A
Agq-1lua Inadequate N/A
A�d to Inadequate N/A
Yes No N/A
Approve
Date Reviewed
3/9/2016
VA 22603
REQUEST FOR SITE PLAN COMMENTS
Frederick County Fire Marshal Comment
Mail to:
Frederick County Fire Marshal
Attn: Fire Marshal
1800 Coverstone Drive
Winchester, Virginia 22602
Hand deliver to:
Public Safety Building
1080 Coverstone Drive
Winchester, Virginia 22602
Phone: (540) 665-6350
Applicant: It is your responsibility to complete t his form as accurately as possible in order to assist the agency with their
review. Please attach two (2) copies of the Site Plan with this sheet.
Applicants Name: George Stickman
Mailing Address:
Howard Shockey & Sons, Inc.
Telephone: 540-723-4133 _
P.O_ Box 2530 r'.
Winchester, VA 22604 ,5 �; n —a-/ N 1L
Name of development and/or description of the request:
Kingspan Insulation –Manufacturing Facility Building & Renovations
Location of Property:
Kingspan Insulation, LLC
172 Partiv Wav
Winchester, VA 22603
Fire Marshal Comments:
5 APPROVED
FIRE MARSHAL, FREDERICK COUNTY
-FREDERICK COUNTY FIRE MARSHAL USE ONLY -
Date Received, +_ Review Numbed` I JZ 3 4 5 (circle one)
Date Reviewed _ _���(D l /�
Revision Required_ Date Approved
Signature & Date:
** Please Return Form to Applicant**
20 1 RE-CEIVCC FEB 29 2efj
REQUEST FOR SITE PLAN COMMENTS
Frederick County Sanitation Authority Comment
Mail to: Land deliver to:
Frederick County Sanitation Authority FCSA
Attn: Engineer 315 Tasker Road
P.O. Box 1877 Stephens City, Virginia 22655
Stephens City, Virginia 22655 Phone: (540) 868-1061
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please attach two (2) copies of the Site Plan with this shcet. j
Applicants Name: George Stickman
Mailing Address: Howard Shockey & Sons: Inc.—
P.O. Box 2530
Winchester, VA 22604
Name of development and/or description of the request:
Kingspan Insulation - Manufacturing Facility Addition & Renovations
Location of Property:
Kingspan Insulation, LLC
172 Pactiv Way
Winchester, VA 22603
FCSA:
0 C6YV)Mj5M r5
Telephone: 540-723-4133
-FREDERICK COUNTY SANITATION AUTHORITY USE ONLY- I
Date Received — _ Review Number 12 3 4 5 (circle
Date Reviewed
Revision Required.- _ _ Date Approved
Signature & Date:
** Please Return Form to Applicant**