HomeMy WebLinkAbout17-17 Commentsn
P:�QST ]FOR Sl�><�� Y'f.A.I��T Cl�Rig4lTS
Frederick County Inspections
Department Comment
M:til to:
Frederick Counter Inspections Department
Attn: Building Official
107 North Xent Street,
0ifinchester, Virginia 22601
Hand deliver to:
Frederick County Inspections Dept.
107 North Kent Street, 2nd Floor
Winchester;, Virginia 22601
Phone: (5413)665-5650
Applicant: It is your responsibility to complete this form as accurately as possible in order to assist the agency with their
review. Please, attach two co nes of the Site P1ar� with LM sheet
:"s'il. �. ,� �,:. ,Yen. k��'.�,�•a•r..,� _� _ap.. �.• av::S4�,Z:icC:Y+lsz _.R r--�..—_ _.... .... -..... < .�, .. ,.; , . .. .. . _. _ .
Awl' ant's Dame: Greenway Enginearing, Inc
Mailing Address
151 Windy Hill Lane
Winchester, VA 22602
Telephone: 5,10-662-4185
Larne of development and/or description of the request:
Thermo Fisher Scientific -Generator Pad, Chiller Pad, Hazardous Waste Container Relocation, New Flammable Raw Material Container location.
Location of Property:
6365 Valley Pike, Middletown
inspections Department Cornmen s:
-F—RE-1 I IEIRICK t OUNITY :a f4dSt EC -11 � NS DE,1PA R fi ATEP 1 USE- t✓ ()Iq -ji -
Bate Received -1 e—;
C. Review )<?urnber l�?, 3 4 5 (circle one)
Bate Reviewed q1 vL 1 -1 -1 k.,j t I
Revision RegW ed � _� Bate Approved -7)1011-1
11
is
JUL - 6 2017
GREENWAY
ENGINEERING
Prefabricated hazardous storage buildings shall comply with The Virginia U fbnn .statewide
Buiiiding Code and Sectons 307, High Hazardous cup 1, and Section 141114r, l--tazardous
Materials of the Virginia Building Code/2012. Other Code that applies is 2012 Virginia Fire
Code.
Hazardous materials shall be classified according to their hazard category. Fire separation
distance to main building shall comply with Section 415 of the Virginia 1303ding Code. Existing
building is Type 1113 unlimited area building. Que-tion: on the location of d -he hazardous
storage container.
Prefabricated Hazardous storage buildings shall be listed an approved as required in the 2012
Virginia Fire Code and shall include an automatic fire extinguishing system.
Ali MSDS sheets are required to be submitted with building permit application, along with
maximum quantities to be stored
Special inspection requirements of Chapter 17 of aBC shall apply to this type of structure. (soils,
concrete, steel etc.)
7/6/17 MSDS Sheets and maximum quantities stored shall be submitted with the permit
application. All prefabricated storage facilities shall be listed and labeled for the proposed use.
Location of containers shall comply with the Virginia Construction Code, 2012 & the Virginia
Fire Code 2012
s:\site plan comments\2012\hazardous storage cor,tainers.doc
Date Received
4/6!2017
Frederick Cowin
Department of Fire and Rescme
Office of the Fire Marsfial
1081) a overs.an Drive H inches;er, VA 226021
(.540) 665-6350 Fax: (540) 678-4739 Ernail:,;fino(afi-va.us
Plan Review &. Comments
Plan/Permit Type Site Plan 04-06-17
Name Thermo Fisher Scientific
Address 8365 Valley PIKE Middletown
Project Name Generator & Chiller Pad
Applicant Name & Number Greenway Engineering 540-662-4185
RE#
Permit Number
Emergency Vehicle Access:
Hydrant Location:
Siamese Location:
Fire Lanes Required.-
Plan
equired:
Plan Approval Status
Comments
Adegtfate Inadequate
N/A
Ad,etf ate Inadequate
N/A
Adequate Inadequate
411
Yes No
AWA
Approvre
-`
Signature: _
Reviewed By: Kenneth Scott, Jr.
Title:
Date Reviewed
4/19/2017