HomeMy WebLinkAbout01-08 Comments (2)April 7, 2008 Mr. Jack Valetti, PE Davis Floyd, Inc. 15 Brendan Way Greenville, South Carolina 29615 Re: Second Review Comments for Site Plan #01 -08; Winchester Industrial Properties Property Identification Number (PIN): 54 -A -36T Dear Mr. Valetti: Planning Staff has reviewed the above referenced site plan to determine if administrative approval can be granted. At this time, administrative approval cannot be granted. This site plan is denied until the issues in this letter, as well as all issues of the other review agencies, have been adequately addressed. Please review Staffs comments listed below and then prepare a revised site plan which adequately addresses each concern. 1) Sheet Index. The sheet index in not correct. In the plans there was not 106A, the road sheets (510- 521) were not indexed, and there is only one landscaping sheet. 2) Doors. Show all loading doors and loading areas for both buildings (a symbol such as atriangle could be used). The plan currently states to see the architectural plans; the doors need to be shown on the site plan. 3) Dumpsters. If any dumpsters will be utilized on the site, they need to be shown on the plan. If none are proposed, provide a note on sheet C -105. 4) Sign Location. The freestanding signs need to be relocated as indicated on sheet C -105. 5) Lighting. Indicate if any wall pack or pole lighting is proposed for the site. If so, locations and details need to be provided on the site plan. After you have revised the site plan, please resubmit two copies so that I may verify the information contained on the plan. 1 will need all approved review agency comment sheets and at least five copies of the final plan for approval. Comment sheets are required from the following agencies: Frederick County Fire Marshal, Frederick County Department of Building Inspections, Frederick County Department of Public Works, Frederick County Department ofG.I.S., Frederick County Sanitation Authority, and the Virginia Department of Transportation. Sincerely, Lt te E. 4(4> Candice E. Perkins, AICP Senior Planner Review Comments: Department of Planning and Development 540/665 -5651 FAX: 540/665 -6395 cc: Johnson Development Associates, Inc., Attn: Scott Scheel, 340 E. Main Street, Ste. 500, Spartanburg, SC 29302 Attachments CEP /bad 107 North Kent Street, Suite 202 Winchester, Virginia 22601 -5000 LI FILE COPY COUNTY of FREDERICK 4 January 24, 2008 U CO► ICK Department of Planning and Development 540/665 -5651 FAX: 540/665-6395 Mr. Jack Valetti, PE Davis Floyd, Inc. 15 Brendan Way Greenville, South Carolina 29615 Re: Review Comments for Site Plan #01 -08; Winchester Industrial Properties Property Identification Number (PIN): 54 -A -36T Dear Mr. Valetti: Planning Staff has reviewed the above referenced site plan to determine if administrative approval can be granted. At this time, administrative approval cannot be granted. This site plan is denied until the issues in this letter, as well as all issues of the other review agencies, have been adequately addressed. Please review Staff's comments listed below and then prepare a revised site plan which adequately addresses each concern. Review Comments: I) Special Limited Power of Attorney Form. Please have the property owner sign the attached Special Limited Power of Attorney Form prior to further review or approval. This form should be notarized and completed to grant the applicant (you) with authorization to represent them for this site plan. 2) Property Identification Number (PIN). The PIN number on the coversheet is incorrect. 3) Project Summary. The project summary on the coversheet is incomplete. Provide the actual BRL's and the actual FAR. 4) Maximum Height. The maximum height in the M1 is 60 feet, not 75 feet. 5) Slat-laze. The coversheet shows 40 foot signs with 100sf, but sheet C -105 shows 50sf signs. The proposed signage should be revised to show 12 foot tall 50sf monument signs to reflect the proposed changes to the County's sign ordinance. 6) Adjoining Properties. Label all adjoining properties. 7) Brooke Road. Show the complete Brooke Road extension on this site plan (all striping, etc.). 8) Trailer Parking Areas. Ensure that all trailer parking areas have curb and gutter. 9) Building 1 Parking. The curb and gutter between the two vehicle parking areas is not needed. 10) Building 2 Parking. On sheet C -105, the building 2 parking data is incorrect. Building 2 is shown with two office areas but only one is shown with parking. 11) Future Parking. All areas labeled future parking should actually show the intended parking layout. Site plans are valid for five years and the parking could be labeled phase 2. If the parking is labeled as phase 2, it could be constructed at a later time. 12) Handicap Parking. The HC parking for building 1 is not labeled and both buildings need to show ramps for the HC parking. 107 North Kent Street, Suite 202 Winchester, Virginia 22601 -5000 Mr: Jack Valetti, PE Davis Floyd, Inc. RE: Winchester lndustrial P rties January 24, 2008 Page 2 13) Acreage Summary and FAR. The FAR on sheet C -105 does not match the acreage provided /building sf. Include in the summary the total amount of the property in ROW. 14) Sidewalk. Extend the sidewalk as indicated on sheet C -105 for building 2. 15) Doors. Show all loading doors and loading areas for both buildings. 16) Dumpsters. If any dumpsters will be utilized on the site, they need to be shown on the plan. 17) Sign Location. The sign adjacent to building 2 could be moved as indicated and the parking expanded. 18) Lighting. Indicate if any wall pack or pole lighting is proposed for the site. If so, locations and details need to be provided. 19) Landscaping Plan. The landscaping plans are not referenced on the coversheet for the most recent site plan submission. Revise the coversheet to include the landscaping plan. 20) Tree Numbers. The landscaping plan states that there are 127 perimeter and interior trees; the plan only accounts for 120. 21) Trailer Storage /Parking Screening. On the landscaping plan, the Holly needs to be 36 inches at time of planting and Magnolia cannot be used. 22) Hedges. A 36 inch evergreen hedge needs to be provided as indicated on the landscaping plan. 23) Trailer Screening. The landscaping plan states that the trailer spaces at the rear of the site will not be screened due to the location of the water line. Not screening the spaces is not an option. If plants cannot be provided, a 6 foot fence will be required. After you have revised the site plan, please resubmit two copies so that 1 may verify the information contained on the plan. I will need all approved review agency comment sheets and at least five copies of the final plan for approval. Comment sheets are required from the following agencies: Frederick County Fire Marshal, Frederick County Department of Building Inspections, Frederick County Department of Public Works, Frederick County Department of G.I.S., Frederick County Sanitation Authority, and the Virginia Department of Transportation. Sincejly, r e 2 f and ice E. Perkins, AICP Senior Planner cc: Patrick Barker, EDC Johnson Development Associates, Inc., Attn: Scott Scheel, 340 E. Main Street, Ste. 500, Spartanburg, SC 29302 Attachments CEP /bad DAVI Engineering rrr �j j r�7 Architecture Y' LIJ i D Environmental Laboratory Services DATE: Dec. 26, 2007 TO: Candice Perkins Dept of Planning 107 North Kent Street Winchester, Va. 22601 PROJECT NAME: Winchester Industrial Development, Building #3 WE ARE SENDING YOU: Attached THE FOLLOWING: COMMENTS: AS FOLLOWS: as requested for your use for distribution for review comment other (see comments below) COPIES 2 sets DATE DWG. NO. DESCRIPTION Site Plans BY: Jack Valetti, PE Under separate cover via: for approval approved approved as noted thereon revise resubmit not approved loaned to you (please return) returned from loan to us for your information Davis Floyd, Inc., 15 Brendan Way, Suite 210, Greenville, SC 29615, Tel 864- 527 -9800, Fax 864 527 -9801 DEC 2 7 2007 DAVIS Q Engineering j Architecture F LO 1 Environmental Laboratory Services DATE: Jan. 4, 2008 TO: Candice Perkins Dept of Planning 107 North Kent Street Winchester, Va. 22601 PROJECT NAME: Winchester Industrial Development WE ARE SENDING YOU: Attached THE FOLLOWING: COPIES 2 sets DATE DWG. NO. DESCRIPTION Plans AS FOLLOWS: as requested for your use for distribution for review comment other (see comments below) COMMENTS: BY: Jack Valetti, PE ?F3ANEMI ?AL Under separate cover via: for approval approved approved as noted thereon revise resubmit JAN 7 2008 not approved loaned to you (please return) returned from loan to us for your information Davis Floyd, Inc., 15 Brendan Way, Suite 210, Greenville, SC 29615, Tel 864-527-9800, Fax 864- 527 -9801 DA�I S FLOYD DATE: TO: Engineering Architecture PROJECT NAME: WE ARE SENDING YOU: Attached THE FOLLOWING: AS FOLLOWS: as requested for your use for distribution for review comment other (see comments below) COMMENTS: Environmental Laboratory Services BY: Jack Valetti, PE n vg 'UAL Feb. 28, 2008 Candice Perkins Dept of Planning 107 North Kent Street Winchester, Va. 22601 Winchester Industrial Development for approval approved approved as noted thereon revise resubmit Under separate cover via: MAR 3 2008 COPIES 2 sets DATE 2 -28 -08 DWG. NO. DESCRIPTION Plans not approved loaned to you (please return) returnedfrom loan to us for your information Davis Floyd, Inc., 15 Brendan Way, Suite 210, Greenville, SC 29615, Tel 864-527 -9800, Fax 864- 527 -9801 /maw Enclosure 1286413 J January 8, 2008 Ms. Candice Perkins Frederick County Planning Department 107 North Kent Street Winchester, VA 22601 Dear Ms. Perkins: Enclosed is the check for the site plan application for the above referenced property. Please let me know if I can be of further assistance. With kind regards, Mendy William 340 E MAIN ST, SUITE 500 SPARTANBURG, SC 29302 JOHNSON DEVELOPMENT ASSOCIATES, INC. INDUSTRIAL MULTI FAMILY REAL ESTATE DEVELOPERS Re: Winchester Industrial Site Pasta Tract PO Box 3524 SPARTANeuRG, SC 29304 JAN 9 2008 P 864.585.2000 I F1354.594.5998 WWW. JOHNSONOEVELOPMENT.NET COMMENTS: Angie Mark Dana Eric Mike John Amber Document Approval Form PLEASE REVIEW THE ATTACHED DOCUMENT. IF THIS DOCUMENT MEETS YOUR APPROVAL PLEASE INITIAL AND PROVIDE THE DATE AND TIME OF YOUR APPROVAL. IF THIS DOCUMENT DOES NOT MEET YOUR APPROVAL PLEASE PROVIDE COMMENTS AS TO WHAT YOU WOULD LIKE TO HAVE COMPLETED. INITIALS DATE TIME Candice 1 I g l e Received by Clerical Staff (Date Time): \SO I U:\Pam \Common\Document Approval Form.wpd JAN 9 2008